4421 Tradition Trail ● Plano, Texas 75093 ● 972 -964-2700 ● 800-836-7472
URL: www.iscenclosurecooling.com ● Email: iscinfo@iscsales.com
SP-ENG-210-100-09 Rev 1.6 15 | P a g e
Heater or Dry Contact
Hysteresis *1
Maximum
Temperature
Alarm
Alerts with “HA” when
maximum temperature has
been exceeded
Minimum
Temperature
Alarm
Alerts with “LA” when
minimum temperature has
been exceeded
*1Note: When both Heater and Dry Contact options are included , these parameters only control Heater
Settings. Dry Contact is controlled by ALU.
Alarms Signals
Start and stop of the compressor after 15 minute
intervals *2
Maximum Temperature Alarm: P1 > 105 °F for 3
minutes (after initial 30 min. start up delay)
Minimum Temperature Alarm: P1 < 45 °F for 3
minutes (after initial 30 min. start up delay)
Condenser High Temperature Alarm: P2 > 145 °F for
3 minutes
Condenser Low Temperature Alarm: P2 < 50°F for 3
minutes
Evaporator Coil Alarm: Low Pressure for 2 minutes
Invalid Probe Selected: Low Evaporator Coil
*2Note: When both Heater and Dry Contact options are included, Dry Contact (Alar m Contact) Relay is
activated.
ALARM RECOVERY……..
If the compressor is turned off due to an alarm, it will be able to restart after the AC anti short-cycle time delay.
(Parameter AC = 5minutes)
Probe alarm P1 is cleared with no time delay after the fault is cleared.
Probe alarm P2 starts and stops with no time delay.
Temperature alarm HA automatically clears as soon as the temperature returns to below 105°F (the ALU setpoint) -2°F = 103°F.
Temperature alarm LA automatically clears as soon as the temperature returns to above 55°F (the ALL setpoint) +2°F = 47°F.
Temperature alarm HA2 automatically clears as soon as the condenser coils temperature returns to below 135°F.
Temperature alarm LA2 automatically clears as soon as the condenser coils temperature returns to above 60°F.
Temperature alarm CA automatically clears as soon as the pressure returns to normal.